74
Commissioning
7.5.1.2
PROFINET IO Fieldbus Couplers 750-375(/025-000), 750-377(/025-000)
When the aforementioned PROFINET IO fieldbus couplers are used, the process
image size is configured by selecting the corresponding GSD entry.
Table 38: PROFINET IO Configuration
Module
750-1491
2 Resistor bridges
(strain gauge)
7.5.2
750-1491 (2AI Resistor Bridge (Strain Gauge))
Parameterization
7.5.2.1
PROFIBUS DP Fieldbus Couplers 750-333(/0xx-000)
On the PROFIBUS DP fieldbus devices, the I/O module can be provided with
operating parameters using the PROFIBUS GSD files under the category
"Device-Specific Parameters".
Figure 30: Example "Device-Specific Parameters" Dialog with PROFIBUS DP
Manual
Version 1.0.0
750-1491 2AI Resistor Bridge (Strain Gauge)
GSD Entry
Sub Module
4AI, INT16[4] I
4AI, {UINT8, INT16}[4] I/O
2AI, INT16[2] I
2AI, {UINT8, INT16}[2] I/O
WAGO I/O System 750
PA Length/
Data Type
[Byte]
Module
I
O
8
n/a
INT16
12
12
{UINT8, INT16}
4
n/a
INT16
6
6
{UINT8, INT16}
Inst.
Sub
Module
4
2