Monitoring/Scaling Settings - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

236 Parameters
No.
Name/Value
45.35
Last month total
energy
-1000000.00 ...
1000000.00 kWh
45.36
Lifetime peak
power value
-3000.00 ...
3000.00 kW
45.37
Lifetime peak
power date
45.38
Lifetime peak
power time
46
46 Monitoring/scaling
settings
46.01
Speed scaling
0.10...30000.00
rpm
46.02
Frequency scaling
0.10...1000.00 Hz
46.03
Torque scaling
0.1...1000.0%
46.04
Power scaling
0.10 ...30000.00
kW or
0.10 ...40200.00 hp
Description
Total energy consumption during the previous month, that is,
between midnight of the first day or the previous month and
midnight of the first day of the present month.
Value of the peak power over the drive lifetime.
Peak power value.
Date of the peak power over the drive lifetime.
Date.
Time of the peak power over the drive lifetime.
Time,
Speed supervision settings; actual signal filtering; general
scaling settings.
Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group
Speed reference
ramp). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.12 Maximum
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in eg.
fieldbus communication.
Acceleration/deceleration terminal/initial speed.
Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group
Frequency reference
chain). The frequency acceleration and
deceleration ramp times are therefore related to this value
(not to parameter
30.14 Maximum
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
Acceleration/deceleration terminal/initial frequency.
Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in eg. fieldbus communication.
Torque corresponding to 10000 on fieldbus.
Defines the output power value that corresponds to 10000 in
eg. fieldbus communication. The unit is selected by
parameter
96.16 Unit
selection.
Power corresponding to 10000 on fieldbus.
23
speed).
28
frequency).
Def/FbEq16
0.00 kWh
0.01 = 1 kWh
0.00 kW
10 = 1 kW
1.1.1980
N/A
00:00:00
N/A
1500.00 rpm;
1800.00 rpm
(95.20
b0)
1 = 1 rpm
50.00 Hz;
60.00 Hz
(95.20
b0)
10 = 1 Hz
100.0%
10 = 1%
1000.00 kW
or hp
1 = 1 unit