ABB ACQ580 Firmware Manual page 161

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
22.21
Constant speed
function
Bit
Name
0
Constant speed
mode
1
Direction
enable
2...15
Reserved
0000h...FFFFh
22.22
Constant speed
sel1
Source defined
by par.
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
Description
Determines how constant speeds are selected, and whether
the rotation direction signal is considered or not when
applying a constant speed.
Information
1 = Packed: 7 constant speeds are selectable using the three sources
defined by parameters 22.22,
0 = Separate: Constant speeds 1, 2 and 3 are separately activated by
the sources defined by parameters 22.22,
In case of conflict, the constant speed with the smaller number takes
priority.
1 = Start dir: To determine running direction for a constant speed, the
sign of the constant speed setting (parameters 22.26...22.32) is
multiplied by the direction signal (forward: +1, reverse: -1). This
effectively allows the drive to have 14 (7 forward, 7 reverse) constant
speeds if all values in
WARNING: If the direction signal is reverse and the active
constant speed is negative, the drive will run in the forward
direction.
0 = Accord Par: The running direction for the constant speed is
determined by the sign of the constant speed setting (parameters
22.26...22.32).
Constant speed configuration word.
When bit 0 of parameter
(Separate), selects a source that activates constant speed 1.
When bit 0 of parameter
(Packed), this parameter and parameters
speed sel2
and
22.24 Constant speed sel3
sources whose states activate constant speeds as follows:
Source defined
22.22
by par.
22.23
0
0
1
0
0
1
1
1
0
0
1
0
0
1
1
1
0 (always off).
1 (always on).
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
22.23
and 22.24.
22.23
22.26...22.32
are positive.
22.21 Constant speed function
22.21 Constant speed function
22.23 Constant
select three
Source defined
Constant speed active
by par.
22.24
0
0
Constant speed 1
0
Constant speed 2
0
Constant speed 3
1
Constant speed 4
1
Constant speed 5
1
Constant speed 6
1
Constant speed 7
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
Parameters 157
Def/FbEq16
0001b
and
22.24
respectively.
1 = 1
is 0
DI3
is 1
None
0
1
2
3
4
5
6

Advertisement

Table of Contents
loading