ABB ACQ580 Firmware Manual page 228

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

224 Parameters
No.
Name/Value
40.47
Set 1 wake-up
deviation
-200000.00...
200000.00 PID
customer units
40.48
Set 1 wake-up
delay
0.00...60.00 s
40.49
Set 1 tracking mode
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
Reserved
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.50
Set 1 tracking ref
selection
Not selected
AI1 scaled
AI2 scaled
FB A ref1
FB A ref2
Other
Description
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay
Set 1 wake-up
delay), the drive wakes up.
See also parameter
40.31 Set 1 deviation
Wake-up level (as deviation between process setpoint and
feedback).
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
deviation.
The delay timer starts when the deviation exceeds the wake-
up level
(40.47 Set 1 wake-up
deviation falls below the wake-up level.
Wake-up delay.
Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter
1 tracking ref selection
is substituted for the PID controller
output. See also section
1 = Tracking mode enabled
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects the value source for tracking mode. See parameter
40.49 Set 1 tracking
mode.
None.
12.12 AI1 scaled value
12.22 AI2 scaled value
03.05 FB A reference 1
03.06 FB A reference 2
Source selection (see
Terms and abbreviations
inversion.
40.47 Set 1 wake-up
deviation), and resets if the
Tracking
(page 59).
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 191).
(see page 191).
(see page 191).
(see page 184).
(see page 184).
(see page 184).
(see page 125).
(see page 126).
(see page 106).
(see page 106).
Def/FbEq16
0.00 PID
customer
units
(40.48
1 = 1 PID
customer unit
0.50 s
1 = 1 s
Not selected
40.50 Set
0
1
2
3
4
5
6
7
8...17
18
19
20
21
22
23
on page 100). -
Not selected
0
1
2
3
4
on page 100). -