Code
Warning / Aux. code
(hex)
A5A0
Safe torque off
Programmable warning:
31.22 STO indication
run/stop
A5EA
Measurement circuit
temperature
A5EB
PU board powerfail
A5ED
Measurement circuit
ADC
A5EE
Measurement circuit
DFF
A5EF
PU state feedback
A5F0
Charging feedback
A682
Flash erase speed
exceeded
A6A4
Motor nominal value
Cause
Safe torque off function is
active, ie safety circuit signal(s)
connected to connector STO is
lost.
Problem with internal
temperature measurement of
the drive.
Power unit power supply
failure.
Measurement circuit fault.
Measurement circuit fault.
State feedback from output
phases does not match control
signals.
Charging feedback signal
missing.
The flash memory (in the
memory unit) has been erased
too frequently, compromising
the lifetime of the memory.
The motor parameters are set
incorrectly.
The drive is not dimensioned
correctly.
0001 Slip frequency is too small.
0002 Synchronous and nominal
speeds differ too much.
0003 Nominal speed is higher than
synchronous speed with 1 pole
pair.
0004 Nominal current is outside
limits
0005 Nominal voltage is outside
limits.
0006 Nominal power is higher than
apparent power.
0007 Nominal power not consistent
with nominal speed and
torque.
Fault tracing 343
What to do
Check safety circuit connections. For
more information, chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
31.22 STO indication
run/stop
(page 180).
Check the value of parameter
Control board
supply.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the feedback signal coming from
the charging system.
Avoid forcing unnecessary parameter
saves by parameter
96.07
parameter writes (such as user logger
triggering through parameters).
Check the auxiliary code (format XYYY
YZZZ). "X" specifies the source of
warning (1: generic flash erase
supervision). "ZZZ" specifies the flash
subsector number that generated the
warning.
Check the auxiliary code. See actions
for each code below.
Check the settings of the motor
configuration parameters in groups 98
and 99.
Check that the drive is sized correctly
for the motor.
95.04
or cyclic

Advertisement

Table of Contents
loading

Table of Contents