ABB ACQ580 Firmware Manual page 165

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
DI1
DI2
DI3
DI4
DI5
DI6
Reserved
Timed function 1
Timed function 2
Timed function 3
Reserved
Supervision 1
Supervision 2
Supervision 3
Other [bit]
22.74
Motor
potentiometer down
source
22.75
Motor
potentiometer ramp
time
0.0...3600.0 s
22.76
Motor
potentiometer min
value
-32768.00...
32767.00
22.77
Motor
potentiometer max
value
-32768.00...
32767.00
22.80
Motor
potentiometer ref
act
-32768.00...
32767.00
Description
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects the source of motor potentiometer down signal.
0 = No change
1 = Decrease motor potentiometer value. (If both the up and
down sources are on, the potentiometer value will not
change.)
For the selections, see parameter
up
source.
Defines the change rate of the motor potentiometer. This
parameter specifies the time required for the motor
potentiometer to change from minimum (22.76) to maximum
(22.77). The same change rate applies in both directions.
Motor potentiometer change time.
Defines the minimum value of the motor potentiometer.
Note: If vector control mode is used, value of this parameter
must be changed.
Motor potentiometer minimum.
Defines the maximum value of the motor potentiometer.
Note: If vector control mode is used, value of this parameter
must be changed.
Motor potentiometer maximum.
The output of the motor potentiometer function. (The motor
potentiometer is configured using parameters 22.71...22.74.)
This parameter is read-only.
Value of motor potentiometer.
Parameters 161
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 191).
(see page 191).
(see page 191).
(see page 184).
(see page 184).
(see page 184).
on page 100). -
22.73 Motor potentiometer
Def/FbEq16
2
3
4
5
6
7
8...17
18
19
20
21...23
24
25
26
Not selected
40.0 s
10 = 1 s
-50.00
1 = 1
50.00
1 = 1
-
1 = 1

Advertisement

Table of Contents
loading

Table of Contents