252 Parameters
No.
Name/Value
58.31
EFB act1
transparent source
Not selected
Other
58.32
EFB act2
transparent source
Not selected
Other
58.33
Addressing mode
Mode 0
Mode 1
Mode 2
58.34
Word order
HI-LO
LO-HI
58.101 Data I/O 1
None
CW 16bit
Ref1 16bit
Description
Selects the source of actual value 1 when parameter
EFB act1 type is set to
Transparent.
None.
Source selection (see
Terms and abbreviations
Selects the source of actual value 2 when parameter
EFB act2 type is set to
Transparent.
None.
Source selection (see
Terms and abbreviations
Defines the mapping between parameters and holding
registers in the 400101...465535 Modbus register range.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
16-bit values (groups 1...99, indexes 1...99):
Register address = 400000 + 100 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 2200 + 80 = 402280.
32-bit values (groups 1...99, indexes 1...99):
Register address = 420000 + 200 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 420000 + 4400 + 160 = 424560.
16-bit values (groups 1...255, indexes 1...255):
Register address = 400000 + 256 × parameter group +
parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 5632 + 80 = 405712.
32-bit values (groups 1...127, indexes 1...255):
Register address = 400000 + 512 × parameter group +
2 × parameter index. For example, parameter 22.80 would be
mapped to register 400000 + 11264 + 160 = 411424.
Selects in which order 16-bit registers of 32-bit parameters
are transferred.
For each register, the first byte contains the high order byte
and the second byte contains the low order byte.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
The first register contains the high order word, the second
contains the low order word.
The first register contains the low order word, the second
contains the high order word.
Defines the address in the drive which the Modbus master
accesses when it reads from or writes to the register address
corresponding to Modbus register 1 (400001).
The master defines the type of the data (input or output). The
value is transmitted in a Modbus frame consisting of two 16-
bit words. If the value is 16-bit, it is transmitted in the LSW
(least significant word). If the value is 32-bit, the subsequent
parameter is also reserved for it and must be set to None.
No mapping, register is always zero.
ABB Drives
profile: 16-bit ABB drives control word;
Profile: lower 16 bits of the DCU control word
Reference REF1 (16 bits)
58.28
on page 100). -
58.29
on page 100). -
58.06
settings).
58.06
settings).
DCU
Def/FbEq16
Not selected
0
Other
(par.
01.07 Motor
current)
0
Mode 0
0
1
2
LO-HI
0
1
CW 16bit
0
1
2