ABB ACQ580 Firmware Manual page 139

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
15.05
RO/DO force
selection
Bit
Value
0
1 = Force RO4 to value of bit 0 of parameter
1
1 = Force RO5 to value of bit 1 of parameter
2...4
Reserved
5
1 = Force DO1 to value of bit 5 of parameter
6...15
Reserved
0000h...FFFFh
15.06
RO/DO forced data
Bit
Name
0
RO4
1
RO5
2...4
Reserved
5
DO1
6...15
Reserved
0000h...FFFFh
15.07
RO4 source
Not energized
Energized
Ready run
Reserved
Enabled
Started
Magnetized
Running
Ready ref
At setpoint
Reverse
Zero speed
Description
The electrical statuses of the relay/digital outputs can be
overridden for eg. testing purposes. A bit in parameter
RO/DO forced data
is provided for each relay or digital output,
and its value is applied whenever the corresponding bit in this
parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
15.05
and 15.06).
Override selection for relay/digital outputs.
Allows the data value of a forced relay or digital output to be
changed from 0 to 1. It is only possible to force an output that
has been selected in parameter
Bits 0...1 are the forced values for RO4...RO5; bit 5 is the
forced value for DO1.
Description
Force the value of this bit to RO4, if so defined in parameter
force
selection.
Force the value of this bit to RO5, if so defined in parameter
force
selection.
1Force the value of this bit to DO1 if so defined in parameter
force
selection.
Forced values of relay/digital outputs.
Selects a drive signal to be connected to relay output RO4.
Output is not energized.
Output is energized.
Bit 1 of
06.11 Main status word
Bit 0 of
06.16 Drive status word 1
Bit 5 of
06.16 Drive status word 1
Bit 1 of
06.17 Drive status word 2
Bit 6 of
06.16 Drive status word 1
Bit 2 of
06.11 Main status word
Bit 8 of
06.11 Main status word
Bit 2 of
06.19 Speed control status word
Bit 0 of
06.19 Speed control status word
15.06
15.06 RO/DO forced
data.
15.06 RO/DO forced
data.
15.06 RO/DO forced
data.
15.05 RO/DO force
selection.
(see page 111).
(see page 112).
(see page 112).
(see page 112).
(see page 112).
(see page 111).
(see page 111).
(see page 113).
(see page 113).
Parameters 135
Def/FbEq16
0000h
1 = 1
0000h
15.05 RO/DO
15.05 RO/DO
15.05 RO/DO
1 = 1
Not
energized
0
1
2
3
4
5
6
7
8
9
10
11