ABB ACQ580 Firmware Manual page 366

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

362 Fault tracing
Code
Fault / Aux. code
(hex)
0xD403
Low level
Programmable fault:
LC low level action
0xD404
Running dry
Programmable fault:
Dry run protection
Cause
Water level is reached the low
level limit. Level control is
76.92
unable to control the level for
the following reasons:
• running out of pumping
capacity or
• analog feedback sensor
failure.
Dry run protection is activated.
82.20
What to do
Check the analog level sensor.
Check that all pumps are operating
normally.
Check parameters
76.90 LC low level
switch
and
76.92 LC low level
Check the pump inlet for sufficient
water level.
Check dry run protection settings in
parameters
82.20 Dry run protection
and
82.21 Dry run
source.
action.