No.
Name/Value
46.05
Current scaling
0...30000 A
46.06
Speed ref zero
scaling
0.00 ... 30000.00
rpm
46.11
Filter time motor
speed
2...20000 ms
46.12
Filter time output
frequency
2...20000 ms
46.13
Filter time motor
torque
2...20000 ms
46.14
Filter time power
2...20000 ms
46.21
At speed hysteresis
0.00...30000.00
rpm
Description
Defines the 16-bit scaling of current parameters. The value of
this parameter corresponds to 10000 in fieldbus
communication.
Defines a speed corresponding to a zero reference received
from fieldbus (either the embedded fieldbus interface, or
interface FBA A). For example, with a setting of 500, the
fieldbus reference range of 0...20000 would correspond to a
speed of 500...[46.01] rpm.
Note: This parameter is effective only with the ABB Drives
communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a filter time for signals
01.02 Motor speed
estimated.
Motor speed signal filter time.
Defines a filter time for signal
Output frequency signal filter time.
Defines a filter time for signal
Motor torque signal filter time.
Defines a filter time for signal
Output power signal filter time.
Defines the "at setpoint" limits for speed control of the drive.
When the difference between reference
reference act
7) and the speed
is smaller than
46.21 At speed
considered to be "at setpoint". This is indicated by bit 8 of
06.11 Main status
word.
Drive at setpoint
(06.11
bit 8 = 1)
Limit for "at setpoint" indication in speed control.
01.01 Motor speed used
01.06 Output
frequency.
01.10 Motor
torque.
01.14 Output
power.
(22.87 Speed
(24.02 Used speed
feedback)
hysteresis, the drive is
24.02
(rpm)
22.87
+
46.21
(rpm)
22.87
(rpm)
22.87
-
46.21
(rpm)
0 rpm
Parameters 237
Def/FbEq16
10000 A
0.00 rpm
1 = 1 rpm
and
500 ms
1 = 1 ms
500 ms
1 = 1 ms
100 ms
1 = 1 ms
100 ms
1 = 1 ms
50.00 rpm
See par.
46.01