128 Parameters
No.
Name/Value
13

13 Standard AO

13.02
AO force selection
Bit
Value
0
1 = Force AO1 to value of parameter
1
1 = Force AO2 to value of parameter
2...15
Reserved
0000h...FFFFh
13.11
AO1 actual value
0.000...22.000 mA /
0.000...11.000 V
13.12
AO1 source
Zero
Motor speed used
Reserved
Output frequency
Motor current
Motor current % of
motor nominal
Motor torque
DC voltage
Output power
Reserved
Speed ref ramp in
Speed ref ramp out
Speed ref used
Reserved
Freq ref used
Reserved
Process PID out
Reserved
Temp sensor 1
excitation
Temp sensor 2
excitation
Description
Configuration of standard analog outputs.
The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
13.02
and 13.11).
Forced values selector for analog outputs AO1 and AO2.
Displays the value of AO1 in mA or V.
This parameter is read-only.
Value of AO1.
Selects a signal to be connected to analog output AO1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 103).
01.08 Motor current % of motor nom
01.10 Motor torque
(page 103).
01.11 DC voltage
(page 103).
01.14 Output power
(page 104).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
28.02 Frequency ref ramp output
40.01 Process PID output actual
The output is used to feed an excitation current to the
temperature sensor 1, see parameter
source. See also section
The output is used to feed an excitation current to the
temperature sensor 2, see parameter
source. See also section
13.13 AO1 forced
value. (0 = Normal mode)
13.23 AO2 forced
value. (0 = Normal mode)
(page 103).
(page 103).
(page 103).
(page 162).
(page 162).
(page 163).
(page 167).
(page 213).
35.11 Temperature 1
Motor thermal protection
35.21 Temperature 2
Motor thermal protection
Def/FbEq16
0000h
1 = 1
-
1 = 1 mA
Output
frequency
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17...19
20
(page 84).
21
(page 84).