354 Fault tracing
Code
Fault / Aux. code
(hex)
5090
STO hardware failure
5091
Safe torque off
Programmable fault:
STO indication run/stop
5092
PU logic error
5093
Rating ID mismatch
5094
Measurement circuit
temperature
5098
I/O communication
loss
50A0
Fan
5682
Power unit lost
5691
Measurement circuit
ADC
5692
PU board powerfail
5693
Measurement circuit
DFF
5696
PU state feedback
5697
Charging feedback
5698
Unknown PU fault
6181
FPGA version
incompatible
6306
FBA A mapping file
Cause
0002 Auxiliary fan 2 broken.
STO hardware diagnostics has
detected hardware failure.
Safe torque off function is
active, ie. safety circuit
31.22
signal(s) connected to
connector STO is broken
during start or run.
Power unit memory has
cleared.
The hardware of the drive does
not match the information
stored in the memory. This
may occur eg. after a firmware
update.
Problem with internal
temperature measurement of
the drive.
Internal standard I/O
communication failure.
Cooling fan stuck or
disconnected.
Connection between the drive
control unit and the power unit
is lost.
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
State feedback from output
phases does not match control
signals.
Charging feedback signal
missing.
The power unit logic has
generated a fault which is not
known by the software.
Firmware and FPGA versions
are incompatible.
Fieldbus adapter A mapping
file read error.
What to do
Contact your local ABB
representative for hardware
replacement.
Check safety circuit connections. For
more information, see chapter The
Safe torque off function in the
Hardware manual of the drive and
description of parameter
indication run/stop
(page 180).
Check the value of parameter
Control board
supply.
Contact your local ABB
representative.
Cycle the power to the drive. You may
have to be repeat this.
Contact your local ABB
representative.
Try resetting the fault or reboot the
drive.
Check fan operation and connection.
Replace fan if faulty.
Check the connection between the
control unit and the power unit.
Contact your local ABB
representative.
Contact your local ABB
representative.
Contact your local ABB
representative.
Contact your local ABB
representative.
Check the feedback signal coming
from the charging system
Check the logic and software
compatibility.
Reboot the control unit (using
parameter
96.08 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative
Contact your local ABB
representative.
31.22 STO
95.04
boot)