ABB ACQ580 Firmware Manual page 144

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

140 Parameters
No.
Name/Value
15.34
Freq out 1 src min
-32768.000...
32767.000
15.35
Freq out 1 src max
-32768.000...
32767.000
15.36
Freq out 1 at src
min
0 ... 16000 Hz
15.37
Freq out 1 at src
max
0 ... 16000 Hz
Description
Defines the real value of the signal (selected by parameter
15.33 Freq out 1
source) that corresponds to the minimum
value of frequency output 1 (defined by parameter
out 1 at src
min). This applies when
is set to
Frequency
output.
(Hz)
15.37
15.36
15.34
(Hz)
15.37
15.36
15.35
Real signal value corresponding to minimum value of
frequency output 1.
Defines the real value of the signal (selected by parameter
15.33 Freq out 1
source) that corresponds to the maximum
value of frequency output 1 (defined by parameter
out 1 at src
max). This applies when
is set to
Frequency
output.
See parameter
15.34 Freq out 1 src
Real signal value corresponding to maximum value of
frequency output 1.
Defines the minimum output value of frequency output 1
when
15.22 DO1 configuration
See also drawing at parameter
Minimum frequency output 1 value.
Defines the maximum value of frequency output 1 when
15.22 DO1 configuration
See also drawing at parameter
Maximum value of frequency output 1.
15.22 DO1 configuration
15.35
Signal (real)
selected by par.
15.33
15.34
Signal (real)
selected by par.
15.33
15.22 DO1 configuration
min.
is set to
Frequency
15.34 Freq out 1 src
is set to
Frequency
output.
15.34 Freq out 1 src
Def/FbEq16
0.000
15.36 Freq
1 = 1
1500.000;
1800.000
15.37 Freq
(95.20
b0)
1 = 1
0 Hz
output.
min.
1 = 1 Hz
16000 Hz
min.
1 = 1 Hz