ABB ACQ580 Firmware Manual page 189

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
32.05
Supervision 1
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
Hysteresis
32.06
Supervision 1
action
No action
Warning
Fault
Fault if running
32.07
Supervision 1
signal
Zero
Speed
Reserved
Frequency
Current
Reserved
Torque
DC voltage
Output power
AI1
AI2
Reserved
Speed ref ramp in
Description
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter 32.07) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Action is taken whenever the signal rises above the value
defined by the limit + 0.5 · hysteresis range
Supervision 1
hysteresis). The action is deactivated when the
signal falls below the value defined by the limit - 0.5 ·
hysteresis range.
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B0 ABB Signal supervision 1
Drive trips on fault
80B0 Signal supervision
If running, the drive trips on fault
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 103).
01.10 Motor torque
(page 103).
01.11 DC voltage
(page 103).
01.14 Output power
(page 104).
12.11 AI1 actual value
(page 125).
12.21 AI2 actual value
(page 126).
23.01 Speed ref ramp input
(32.09
and
32.10
respectively).
(32.11
is generated.
1.
80B0 Signal supervision
(page 103).
(page 103).
(page 162).
Parameters 185
Def/FbEq16
Disabled
0
1
2
3
4
5
6
7
No action
0
1
2
1.
3
Frequency
0
1
2
3
4
5
6
7
8
9
10
11...17
18