ABB ACQ580 Firmware Manual page 183

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
Supervision 3
Other [bit]
31.12
Autoreset selection
Bit
Fault
0
Overcurrent
1
Overvoltage
2
Undervoltage
3
AI supervision fault
4...9
Reserved
10
Selectable fault (see parameter
11
External fault 1 (from source selected by parameter
12
External fault 2 (from source selected by parameter
13
External fault 3 (from source selected by parameter
14
External fault 4 (from source selected by parameter
15
External fault 5 (from source selected by parameter
0000h...FFFFh
31.13
Selectable fault
0000h...FFFFh
31.14
Number of trials
0...5
31.15
Total trials time
1.0...600.0 s
31.16
Delay time
0.0...120.0 s
31.19
Motor phase loss
No action
Fault
Description
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
WARNING! Before you activate the function, make
sure that no dangerous situations can occur. The
function restarts the drive automatically and continues
operation after a fault.
The bits of this binary number correspond to the following
faults:
31.13 Selectable
Automatic reset configuration word.
Defines the fault that can be automatically reset using
parameter
31.12 Autoreset
Faults are listed in chapter
Fault code.
Defines the number of automatic fault resets the drive
performs within the time defined by parameter
trials
time.
Number of automatic resets.
Defines the time the automatic reset function will attempt to
reset the drive. During this time, it will perform the number of
automatic resets defined by
Time for automatic resets.
Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter
Autoreset
selection.
Autoreset delay.
Selects how the drive reacts when a motor phase loss is
detected.
No action taken.
The drive trips on fault
3381 Output phase
(see page 184).
on page 100). -
fault)
31.01 External event 1
31.03 External event 2
31.05 External event 3
31.07 External event 4
31.09 External event 5
selection, bit 10.
Fault tracing
(page 351).
31.15 Total
31.14 Number of
trials.
31.12
loss.
Parameters 179
Def/FbEq16
26
000Ch
(00...1100b)
source)
source)
source)
source)
source)
1 = 1
0000h
10 = 1
5
10 = 1
30.0 s
10 = 1 s
5.0 s
10 = 1 s
Fault
0
1