ABB ACQ580 Firmware Manual page 286

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

282 Parameters
No.
Name/Value
Svenska
Russki
Cesky
96.02
Pass code
0...99999999
96.03
Access level status
Bit
Name
0
End user
1
Service
2
Advanced programmer
3...10
Reserved
11
OEM access level 1
12
OEM access level 2
13
OEM access level 3
14
Parameter lock
15
Reserved
00000000h...
FFFFFFFFh
96.06
Parameter restore
Done
Description
Swedish.
Russian.
Czech.
Pass codes can be entered into this parameter to activate
further access levels (see parameter
status) or to configure the user lock.
Entering "358" toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, "10000000") enables
parameters 96.100...96.102, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters 96.100...96.102. After entering the code,
check that the parameters are in fact hidden. If they are not,
enter another (random) pass code.
Note: You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a safe
place – the protection cannot be disabled even by ABB if the
code is lost.
See also section
User lock
Pass code.
Shows which access levels have been activated by pass
codes entered into parameter
Active access levels.
Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Restoring is completed.
96.03 Access level
(page 97).
96.02 Pass
code.
Def/FbEq16
1053
1049
1029
-
0001b
-
Done
0

Advertisement

Table of Contents
loading

Table of Contents