358 Fault tracing
Code
Fault / Aux. code
(hex)
80A0
AI supervision
Programmable fault:
12.03 AI supervision
function
80B0
Signal supervision 1
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
80B3
Signal supervision 4
(Editable message text)
Programmable fault:
32.36 Supervision 4 action
80B4
Signal supervision 5
(Editable message text)
Programmable fault:
32.46 Supervision 5 action
80B5
Signal supervision 6
(Editable message text)
Programmable fault:
32.56 Supervision 6 action
9081
External fault 1
(Editable message text)
Programmable fault:
External event 1 source
31.02 External event 1
type
9082
External fault 2
(Editable message text)
Programmable fault:
External event 2 source
31.04 External event 2
type
9083
External fault 3
(Editable message text)
Programmable fault:
External event 3 source
31.06 External event 3
type
Cause
An analog signal is outside the
limits specified for the analog
input.
0001 AI1LessMIN
0002 AI1GreaterMAX
0003 AI2LessMIN.
0004 AI2GreaterMAX
Fault generated by the signal
supervision function 1.
Fault generated by the signal
supervision function 2.
Fault generated by the signal
supervision function 3.
Fault generated by the signal
supervision function 4.
Fault generated by the signal
supervision function 5.
Fault generated by the signal
supervision function 6.
Fault in external device 1.
31.01
Fault in external device 2.
31.03
Fault in external device 3.
31.05
What to do
Check signal level at the analog input.
Check the auxiliary code.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
12 Standard
AI.
Check the source of the fault
(parameter
32.07 Supervision 1
signal).
Check the source of the fault
(parameter
32.17 Supervision 2
signal).
Check the source of the fault
(parameter
32.27 Supervision 3
signal).
Check the source of the fault
(parameter
32.37 Supervision 4
signal).
Check the source of the fault
(parameter
32.47 Supervision 5
signal).
Check the source of the fault
(parameter
32.57 Supervision 6
signal).
Check the external device.
Check setting of parameter
External event 1
source.
Check the external device.
Check setting of parameter
External event 2
source.
Check the external device.
Check setting of parameter
External event 3
source.
31.01
31.03
31.05