Setting Up The Embedded Fieldbus Interface - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Fieldbus control through the embedded fieldbus interface (EFB) 365

Setting up the embedded fieldbus interface

Set the drive up for the embedded fieldbus communication with the parameters
shown in the table below. The Setting for fieldbus control column gives either the
value to use or the default value. The Function/Information column gives a
description of the parameter.
Parameter
COMMUNICATION INITIALIZATION
58.01
Protocol enable
EMBEDDED MODBUS CONFIGURATION
58.03
Node address
58.04
Baud rate
58.05
Parity
58.14
Communication
loss action
58.15
Communication
loss mode
58.16
Communication
loss time
58.17
Transmit delay
58.25
Control profile
58.26
EFB ref1 type
58.27
EFB ref2 type
58.28
EFB act1 type
58.29
EFB act2 type
Setting for
fieldbus control
Modbus RTU
1 (default)
19.2 kbps
(default) Defines the communication speed of the link.
8 EVEN 1
(default) Selects the parity and stop bit setting. Use the
Fault
(default)
Cw / Ref1 / Ref2
(default)
3.0 s (default)
0 ms (default)
ABB Drives
(default)
Speed or
frequency
(default
for 58.26),
Transparent,
General,Transpare
nt
(default for
58.27) Speed,
Frequency
Speed or
frequency
(default
for 58.28),
Transparent
(default for 58.29),
General, Speed,
Frequency
Function/Information
Initializes embedded fieldbus communication.
Node address. There must be no two nodes
with the same node address online.
Use the same setting as in the master station.
same setting as in the master station.
Defines the action taken when a
communication loss is detected.
Enables/disables communication loss
monitoring and defines the means for
resetting the counter of the communication
loss delay.
Defines the timeout limit for the
communication monitoring.
Defines a response delay for the drive.
Selects the control profile used by the drive.
See section
Basics of the embedded fieldbus
interface
(page 368).
Defines the types of fieldbus references 1 and
2. The
for each reference type is
scaling
defined by parameters 46.01...46.03. With
the
Speed or frequency
selected automatically according to the
currently active drive control mode.
Defines the types of actual values 1 and 2.
The
for each actual value type is
scaling
defined by parameters 46.01...46.03. With
the
Speed or frequency
selected automatically according to the
currently active drive control mode.
setting, the type is
setting, the type is