O Extension Module - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
13.28
AO2 source max
-32768.0...32767.0
13.29
AO2 out at AO2 src
min
0.000 ... 22.000 mA Minimum AO2 output value.
13.30
AO2 out at AO2 src
max
0.000 ... 22.000 mA Maximum AO2 output value.
13.91
AO1 data storage
-327.68...327.67
13.92
AO2 data storage
-327.68...327.67
15
15 I/O extension
module
15.01
Extension module
type
None
CMOD-01
CMOD-02
CHDI-01
CPTC-02
15.02
Detected extension
module
None
Description
Defines the real maximum value of the signal (selected by
parameter
13.22 AO2
source) that corresponds to the
maximum required AO2 output value (defined by parameter
13.30 AO2 out at AO2 src
source
min. See parameter
AO automatic scaling.
Real signal value corresponding to maximum AO2 output
value.
Defines the minimum output value for analog output AO2.
See also drawing at parameter
Defines the maximum output value for analog output AO2.
See also drawing at parameter
Storage parameter for controlling analog output AO1 eg.
through the embedded fieldbus interface.
In parameter
13.12 AO1
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.101...58.114) to
AO1 data
Storage parameter for AO1.
Storage parameter for controlling analog output AO2 eg.
through the embedded fieldbus interface.
In parameter
13.22 AO2
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.101...58.114) to
AO2 data
Storage parameter for AO2.
Configuration of the I/O extension module installed in slot 2.
See also section
Programmable I/O extensions
Note: The contents of the parameter group vary according to
the selected I/O extension module type.
Activates (and specifies the type of) I/O extension module. If
the value is None, when an extension module has been
installed and the dive is powered, the drive automatically sets
the value to the type it has detected (= value of parameter
15.02 Detected extension
Extension I/O configuration failure
to set the value of this parameter manually.
Inactive.
CMOD-01 multifunction extension module (external
24 V AC/DC and digital I/O).
CMOD-02 multifunction extension module (external
24 V AC/DC and isolated PTC interface).
CHDI-01 115/230 V digital input extension module.
CPTC-02 extension module.
I/O extension module detected on the drive.
Inactive.
max). See parameter
13.27 AO2
13.17 AO1 source min
13.27 AO2 source
13.27 AO2 source
source, select
AO1 data
storage.
source, select
AO2 data
storage.
(page 47).
module); otherwise warning
is generated and you have
Parameters 133
Def/FbEq16
about the
1 = 1
0.000 mA
min.
1000 = 1 mA
20.000 mA
min.
1000 = 1 mA
0.00
storage.
100 = 1
0.00
storage.
100 = 1
None
A7AB
0
1
2
3
4
None
0