ABB ACQ580 Firmware Manual page 200

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

196 Parameters
No.
Name/Value
34.42
Timer 11 start time
34.43
Timer 11 duration
34.44
Timer 12
configuration
34.45
Timer 12 start time
34.46
Timer 12 duration
34.60
Season 1 start date
01.01...31.12
34.61
Season 2 start date
34.62
Season 3 start date
34.63
Season 4 start date
34.70
Number of active
exceptions
0...16
Description
See
34.12 Timer 1 start
See
34.13 Timer 1
duration.
See
34.11 Timer 1
configuration.
See
34.12 Timer 1 start
See
34.13 Timer 1
duration.
Defines the start date of season 1 in format dd.mm, where dd
is the number of the day and mm is the number of the month.
The season changes at midnight. One season can be active
at a time. Timers are started on exception days even if they
are not inside the active season.
The season start dates (1...4) must be given in increasing
order to use all seasons. The default value is interpreted that
the season is not configured. If the season start dates are not
in increasing order and the value is something else than the
default value, a season configuration warning is given.
Season start date.
Defines the start date of season 2.
See
34.60 Season 1 start
Defines the start date of season 3.
See
34.60 Season 1 start
Defines the start date of season 4.
See
34.60 Season 1 start
Defines how many of the exceptions are active by specifying
the last active one. All preceding exceptions are active.
Exceptions 1...3 are periods (duration can be defined) and
exceptions 4...16 are days (duration is always 24 hours).
Example: If the value is 4, exceptions 1...4 are active, and
exceptions 5...16 are not active.
Number of active exception periods or days.
time.
time.
date.
date.
date.
Def/FbEq16
00:00:00
00 00:00
0111 1000
0000b
00:00:00
00 00:00
01.01.
01.01.
01.01.
01.01.
3
-