Standard Ai - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

124 Parameters
No.
Name/Value
12

12 Standard AI

12.02
AI force selection
Bit
Value
0
1 = Force AI1 to value of parameter
1
1 = Force AI2 to value of parameter
2...15
Reserved
0000h...FFFFh
12.03
AI supervision
function
No action
Fault
Warning
Last speed
Speed ref safe
12.04
AI supervision
selection
Bit
Name
0
AI1 < MIN
1
AI1 > MAX
2
AI2 < MIN
3
AI2 > MAX
4...15
Reserved
0000h...FFFFh
Description
Configuration of standard analog inputs.
The true readings of the analog inputs can be overridden for
eg. testing purposes. A forced value parameter is provided for
each analog input, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: AI filter times (parameters
12.26 AI2 filter
time) have no effect on forced AI values
(parameters
12.13 AI1 forced value
value).
Note: Boot and power cycle reset the force selections
(parameters
12.02
and 12.03).
Forced values selector for analog inputs AI1 and AI2.
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The inputs and the limits to be observed are selected by
parameter
12.04 AI supervision
No action taken.
Drive trips on
80A0 AI
supervision.
Drive generates an
A8A0 AI supervision
Drive generates a warning
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Drive generates a warning
speed to the speed defined by parameter
safe
(or
28.41 Frequency ref safe
is being used).
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
Specifies the analog input limits to be supervised. See
parameter
12.03 AI supervision
Description
1 = Minimum limit supervision of AI1 active.
1 = Maximum limit supervision of AI1 active.
1 = Minimum limit supervision of AI2 active.
1 = Maximum limit supervision of AI2 active.
Activation of analog input supervision.
12.16 AI1 filter time
and
12.23 AI2 forced
12.13 AI1 forced
value.
12.23 AI2 forced
value.
selection.
warning.
(A8A0 AI
supervision) and freezes
(A8A0 AI
supervision) and sets the
22.41 Speed ref
when frequency reference
function.
Def/FbEq16
0000h
and
1 = 1
No action
0
1
2
3
4
0000h