ABB ACQ580 Firmware Manual page 205

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
Therm(0)
Therm(1)
35.12
Temperature 1 fault
limit
-60...5000 °C or
-76...9032 °F
35.13
Temperature 1
warning limit
-60...5000 °C or
-76...9032 °F
35.14
Temperature 1 AI
source
Not selected
AI1 actual value
AI2 actual value
Other
35.21
Temperature 2
source
Disabled
Estimated
temperature
Reserved
Description
PTC sensor or a normally closed thermistor connected relay
to digital input DI6. The motor is overheated when the digital
input is 0.
Normally open thermistor relay connected to digital input DI6.
The motor is overheated when the digital input is 1.
Defines the fault limit for temperature supervision function 1.
When measured temperature 1 exceeds the limit, the drive
trips on fault
4981 External temperature
The unit is selected by parameter
Note: With a PTC sensor, changing the value of this
parameter has no effect on fault generation. When PTC is
over the triggering threshold of the CMOD-02 (see the
Hardware manual), the drive trips on the fault and when PTC
has decreased below recovery threshold of the CMOD-02
(see the Hardware manual), the fault is reset.
Fault limit for temperature monitoring function 1.
Defines the warning limit for temperature supervision
function 1. When measured temperature 1 exceeds the limit,
warning
A491 External temperature 1
The unit is selected by parameter
Note: With a PTC sensor, changing the value of this
parameter has no effect on warning generation. When PTC is
over the triggering threshold of the CMOD-02 (see the
Hardware manual), the drive trips on the fault and when PTC
has decreased below recovery threshold of the CMOD-02
(see the Hardware manual), the fault is reset.
Warning limit for temperature monitoring function 1.
Specifies the analog input when the setting of
Temperature 1 source
requires measurement through an
analog input.
None.
Analog input AI1 on the control unit.
Analog input AI2 on the control unit.
Source selection (see
Terms and abbreviations
Selects the source from which measured temperature 2 is
read.
Usually this source is from a sensor connected to the motor
controlled by the drive, but it could be used to measure and
monitor a temperature from other parts of the process as long
as a suitable sensor is used as per the selection list.
None. Temperature monitoring function 2 is disabled.
Estimated motor temperature (see parameter
estimated
temperature).
The temperature is estimated from an internal drive
calculation. It is important to set up the ambient temperature
of the motor in
35.50 Motor ambient
Parameters 201
1.
96.16 Unit
selection.
is generated.
96.16 Unit
selection.
35.11
on page 100). -
35.01 Motor
temperature.
Def/FbEq16
21
22
130 °C or
266 °F
1 = 1 °
110 °C or
230 °F
1 = 1 °
Not selected
0
1
2
Disabled
0
1
3...4