ABB ACQ580 Firmware Manual page 280

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

276 Parameters
No.
Name/Value
Fault
82.26
Time-out limit
0.0...1800.0 s
82.30
Outlet minimum
pressure protection
Disabled
Warning
Fault
Warning/Fault
82.31
Outlet minimum
pressure warning
level
0.00...32767.00 bar Outlet minimum pressure warning level.
82.32
Outlet minimum
pressure fault level
0.00...32767.00 bar Outlet minimum pressure fault level.
82.35
Outlet maximum
pressure protection
Disabled
Warning
Fault
Warning/Fault
Description
Generates
D50B Pipe fill-timeout
Defines the delay time at which setpoint must be reached
after last change in PID reference ramp output.
Time-out limit in seconds.
Enables outlet minimum pressure protection function.
Outlet minimum pressure protection function is disabled.
Outlet minimum pressure protection function generates
Outlet minimum pressure
pressure is below the level defined with parameter
Outlet minimum pressure warning level
Pressure check
delay.
Outlet minimum pressure protection function generates
Outlet minimum pressure
pressure is below the level defined with parameter
Outlet minimum pressure fault level
parameter
82.45 Pressure check
Outlet minimum pressure protection function first generates a
warning when the pressure is below the level defined with
parameter
82.31 Outlet minimum pressure warning level
time set in parameter
82.45 Pressure check
If the pressure continues to fall below the level defined with
parameter
82.32 Outlet minimum pressure fault
minimum pressure fault is generated.
Defines the level at which drive should generate the outlet
minimum pressure warning.
Defines the level at which drive should generate the outlet
minimum pressure fault.
Enables outlet maximum pressure protection function.
Outlet maximum pressure protection is disabled.
Outlet maximum pressure protection function generates
D50F Outlet maximum pressure
is above the level defined with parameter
maximum pressure warning level
82.45 Pressure check
delay.
Outlet maximum pressure protection function generates
Outlet maximum pressure
the level defined with parameter
pressure fault level
for a time set in parameter
check
delay.
Outlet maximum pressure protection function first generates
a warning when the pressure is above the level defined with
parameter
82.37 Outlet maximum pressure warning level
a time set in parameter
If the pressure raises above the level defined with parameter
82.38 Outlet maximum pressure fault
pressure fault is generated.
fault.
warning when the outlet minimum
for a time set in
fault when the outlet minimum
for a time set in
delay.
delay.
warning when the pressure
82.37 Outlet
for a time set in parameter
fault when the pressure is above
82.38 Outlet maximum
82.45 Pressure
82.45 Pressure check
delay.
level, outlet maximum
Def/FbEq16
2
60.0
1 = 1 s
Disabled
0
D50E
1
82.31
82.45
D408
2
82.32
3
for a
level, outlet
0.00
1 = 1 bar
0.00
1 = 1 bar
Disabled
0
1
D409
2
3
for