ABB ACQ580 Firmware Manual page 259

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
-200000.00...
200000.0
71.16
Setpoint 1 source
71.19
Internal setpoint
sel1
71.20
Internal setpoint
sel2
71.21
Internal setpoint 1
71.22
Internal setpoint 2
71.23
Internal setpoint 3
71.26
Setpoint min
71.27
Setpoint max
71.31
Deviation inversion
71.32
Gain
71.33
Integration time
71.34
Derivation time
71.35
Derivation filter time
71.36
Output min
71.37
Output max
71.38
Output freeze
enable
71.39
Deadband range
0.0...200000.0
71.40
Deadband delay
0.0...3600.0 s
71.58
Increase prevention
71.59
Decrease
prevention
71.62
Internal setpoint
actual
Description
Process PID controller output base.
See parameter
40.16 Set 1 setpoint 1
See parameter
40.19 Set 1 internal setpoint
See parameter
40.20 Set 1 internal setpoint
See parameter
40.21 Set 1 internal setpoint
See parameter
40.22 Set 1 internal setpoint
See parameter
40.23 Set 1 internal setpoint
See parameter
40.26 Set 1 setpoint
See parameter
40.27 Set 1 setpoint
See parameter
40.31 Set 1 deviation
See parameter
40.32 Set 1
See parameter
40.33 Set 1 integration
See parameter
40.34 Set 1 derivation
See parameter
40.35 Set 1 derivation filter
See parameter
40.36 Set 1 output
See parameter
40.37 Set 1 output
See parameter
40.38 Set 1 output freeze
The control program compares the absolute value of
parameter
71.04 Deviation act value
defined by this parameter. If the absolute value is within the
deadband range for the time period defined by parameter
71.40 Deadband
delay, PID's deadband mode is activated
and
71.06 PID status word
PID's output is frozen and
frozen
is set.
If the absolute value is equal or greater than the deadband
range, PID's deadband mode is deactivated.
Range
Defines the deadband delay for the deadband function. See
parameter
71.39 Deadband
Delay
See parameter
40.58 Set 1 increase
See parameter
40.59 Set 1 decrease
See parameter
40.62 PID internal setpoint
source.
sel1.
sel2.
1.
2.
3.
min.
max.
inversion.
gain.
time.
time.
time.
min.
max.
enable.
to the deadband range
bit 9
Deadband active
is set. Then
71.06 PID status word
bit 2
range.
prevention.
prevention.
actual.
Parameters 255
Def/FbEq16
1 = 1
AI1 percent
Not selected
Not selected
0.00 PID
customer
units
0.00 PID
customer
units
0.00 PID
customer
units
0.00
200000.00
Not inverted
(Ref - Fbk)
1.00
60.0 s
0.000 s
0.0 s
-200000.00
200000.00
Not selected
0.0
Output
1 = 1
0.0 s
1 = 1 s
No
No
-