ABB ACQ580 Firmware Manual page 349

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Code
Warning / Aux. code
(hex)
A780
Motor stall
Programmable warning:
31.24 Stall function
A7AB
Extension I/O
configuration failure
A7C1
FBA A
communication
Programmable warning:
50.02 FBA A comm loss
func
A7CE
EFB comm loss
Programmable warning:
58.14 Communication
loss action
A7EE
Panel loss
Programmable warning:
49.05 Communication
loss action
A88F
Cooling fan
A8A0
AI supervision
Programmable warning:
12.03 AI supervision
function
A8A1
RO life warning
Cause
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Installed CMOD module is not
the same as configured.
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Communication break in
embedded fieldbus (EFB)
communication.
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Maintenance timer limit
exceeded.
An analog signal is outside the
limits specified for the analog
input.
The relay has changed states
more than the recommended
number of times.
0001 Relay output 1
0002 Relay output 2
0003 Relay output 3
Fault tracing 345
What to do
Check motor load and drive ratings.
Check fault function parameters.
Check that the installed module (shown
by parameter
15.02 Detected extension
module) is the same as selected by
parameter
15.01 Extension module
type.
Check status of fieldbus
communication. See user
documentation of fieldbus interface.
Check settings of parameter groups
Fieldbus adapter
(FBA),
settings,
52 FBA A data in
A data
out.
Check cable connections.
Check if communication master is able
to communicate.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Check PC tool or control panel
connection.
Check control panel connector.
Check mounting platform if being used.
Disconnect and reconnect the control
panel.
Consider changing the cooling fan.
Parameter
05.04 Fan on-time counter
shows the running time of the cooling
fan.
Check signal level at the analog input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
Standard
AI.
Change the control board or stop using
the relay output.
Change the control board or stop using
relay output 1.
Change the control board or stop using
relay output 2.
Change the control board or stop using
relay output 3.
50
51 FBA A
and
53 FBA
12