Timed Functions - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
Hysteresis
32.56
Supervision 6
action
No action
Warning
Fault
Fault if running
32.57
Supervision 6
signal
32.58
Supervision 6 filter
time
0.000 ... 30.000 s
32.59
Supervision 6 low
-21474836.00...
21474836.00
32.60
Supervision 6 high
-21474836.00...
21474836.00
32.61
Supervision 6
hysteresis
0.00...100000.00
34

34 Timed functions

34.01
Timed functions
status
Bit
Name
0
Timed function 1
1
Timed function 2
2
Timed function 3
3...15
Reserved
0000h...0FFFFh
Description
Action is taken whenever the signal rises above the value
defined by the limit + 0.5 · hysteresis range
Supervision 6
hysteresis). The action is deactivated when the
signal falls below the value defined by the limit - 0.5 ·
hysteresis range.
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 6
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B5 ABB Signal supervision 6
Drive trips on fault
80B5 Signal supervision
Drive trips on fault
80B0 Signal supervision 1
running.
Selects the signal to be monitored by signal supervision
function 6.
For the available selections, see parameter
Supervision 1
signal.
Defines a filter time constant for the signal monitored by
signal supervision 6.
Signal filter time.
Defines the lower limit for signal supervision 6.
Low limit.
Defines the upper limit for signal supervision 6.
Upper limit.
Defines the hysteresis for the signal monitored by signal
supervision 6.
Hysteresis.
Configuration of the timed functions.
See also section
Timed functions
Status of the combined timers. The status of a combined
timer is the logical OR of all timers connected to it.
This parameter is read-only.
Description
1 = Active.
1 = Active.
1 = Active.
Status of combined timers 1...3.
Parameters 191
(32.61
is generated.
6.
if the motor is
32.07
(page 70).
Def/FbEq16
7
No action
0
1
2
3
Zero
0.000 s
1000 = 1 s
0.00
-
0.00
-
0.00
-
-
1 = 1