ABB ACQ580 Firmware Manual page 353

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Code
Warning / Aux. code
(hex)
0xD506
Pump cleaning not
possible
0xD507
Pump cleaning
needed
0xD508
High level
Programmable warning:
76.93 LC high level action
0xD509
Low level
Programmable warning:
76.92 LC low level action
0xD50A Running dry
Programmable warning:
82.20 Dry run protection
D50C
Maximum flow
protection
Programmable warning:
80.17 Maximum flow
protection
D50D
Minimum flow
protection
Programmable warning:
80.18 Minimum flow
protection
D50E
Outlet minimum
pressure
Programmable warning:
82.30 Outlet minimum
pressure protection
D50F
Outlet maximum
pressure
Programmable warning:
82.35 Outlet maximum
pressure protection
Cause
Pump cleaning cannot be
started. The drive needs to be
in remote control and start
signal is activated.
Dirt detection indicates that the
pump needs cleaning but
automatic pump cleaning is not
allowed.
Water level is reached the high
level limit. Level control is
unable to control the level for
the following reasons:
• running out of pumping
capacity.
• analog feedback sensor
failure.
Water level is reached the low
level limit. Level control is
unable to control the level for
the following reasons:
• running out of pumping
capacity.
• analog feedback sensor
failure.
Dry run protection is activated.
Actual flow is exceeded the
defined warning level.
Actual flow is below the
defined warning level.
Measured outlet pressure is
below the defined warning
limit.
Measured outlet pressure is
above the defined warning
limit.
Fault tracing 349
What to do
Change control location to Auto.
Perform pump cleaning manually.
Start pump cleaning by changing
parameter
83.12 Manually force
cleaning
to
Start cleaning
Check analog level sensor.
Check that all the pumps are operating
normally.
Check parameters
76.91 LC high level
switch
and
76.93 LC high level
Check analog level sensor.
Check that all the pumps are operating
normally.
Check parameters
76.90 LC low level
switch
and
76.92 LC low level
Check the pump inlet for sufficient
water level.
Check dry run protection settings in
parameters
82.20 Dry run protection
and
82.21 Dry run
source.
Check the system for leakages.
Check flow protection settings in
parameters
80.15 Maximum
Maximum flow protection
Flow check
delay.
Check that the inlet and outlet valves
are open.
Check flow protection settings in
parameters
80.16 Minimum
Minimum flow protection
Flow check
delay.
Check the pump outlet for leakages.
Check the configuration of outlet
pressure protection.
See parameters
82.30 Outlet minimum
pressure protection
and
minimum pressure warning
Check the pump outlet for blockages or
closed valve.
Check the configuration of outlet
pressure protection.
See parameters
82.35 Outlet maximum
pressure protection
and
maximum pressure warning
now.
action.
action.
flow,
80.17
and
80.19
flow,
80.18
and
80.19
82.31 Outlet
level.
82.37 Outlet
level.