ABB ACQ580 Firmware Manual page 287

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
Restore defaults
Clear all
Reset all fieldbus
settings
Reset home view
Reset end user
texts
Reset motor data
All to factory
defaults
96.07
Parameter save
manually
Done
Save
96.08
Control board boot
No action
Reboot
Description
Restores all editable parameter values to default values,
except
• motor data and ID run results
• I/O extension module settings
• end user texts, such as customized warnings and faults,
and the drive name
• control panel/PC communication settings
• fieldbus adapter settings
• control macro selection and the parameter defaults
implemented by it
parameter 95.01 Supply voltage
• differentiated defaults implemented by parameters
HW options word 1
• user lock configuration parameters
Restores all editable parameter values to default values,
except
• end user texts, such as customized warnings and faults,
and the drive name
• control panel/PC communication settings
• user lock configuration parameters
• group
49 Panel port communication
Restores all fieldbus and communication related settings to
default values.
Note: Fieldbus, control panel and PC tool communication are
interrupted during the restore.
Restores the home view layout back to show the values of the
default parameters defined by the control macro in use
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning texts,
PID unit and currency unit.
Restores all motor nominal values and motor ID run results to
default values.
• Restores all drive parameters and settings back to initial
factory values.
Saves the valid parameter values to the permanent memory
on the drive control unit to ensure that operation can continue
after cycling the power. Save the parameters with this
parameter
• to store values sent from the fieldbus
• when using external +24 V DC power supply to the control
unit: to save parameter changes before you power down
the control unit. The supply has a very short hold-up time
when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Save completed.
Save in progress.
Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
1 = No action.
1 = Reboot the control unit.
Parameters 283
95.20
96.100...96.102.
96.100...96.102.
parameters.
Def/FbEq16
8
62
32
512
1024
2
34560
Done
0
1
No action
0
1