ABB ACQ580 Firmware Manual page 282

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

278 Parameters
No.
Name/Value
Triggered
83.02
Pump cleaning
progress
0.0...100.0%
83.03
Total cleaning count
0...1000000
83.10
Pump cleaning
action
Off
Cleaning
Warning only
83.11
Pump cleaning
triggers
Bit
Name
0
Reserved
1
Every start
2
Every stop
3
Reserved
4
Overload detection
5
Underload detection
6
Fixed time interval
7
Combined timer1
8...9
Reserved
10
Supervision 1
11
Supervision 2
12
Supervision 3
13
DI4
14
DI5
15
DI6
83.12
Manually force
cleaning
Not active
Start cleaning now
DI4
DI5
DI4
Other [bit]
Description
Cleaning sequence is triggered by parameter
warning generation only.
Displays the pump cleaning progress.
Percentage
Displays the total cleaning count.
Total cleaning count.
Enables the pump cleaning action.
Pump cleaning is disabled.
Pump cleaning is started based on triggers.
Generates warning message based on triggers.
Enables/disables the pump cleaning sequence for the drive,
and defines the triggering conditions.
Note: If DI1 remains On after cleaning is finished, no cleaning
sequence is started. The drive starts cleaning on next start, if
the trigger signal is On when motor is started.
Description
Cleaning starts at every start.
Cleaning starts at every stop.
Cleaning sequence starts when overload situation is
detected. To set up the overload curve, see parameters in
group
37 User load
Cleaning sequence starts when underload situation is
detected. To set up the overload curve, see parameters in
group
37 User load
Time interval defined by parameter
Combined timer 1 of timed functions starts cleaning.
Cleaning sequence starts when Supervision 1 is high.
Cleaning sequence starts when Supervision 2 is high.
Cleaning sequence starts when Supervision 3 is high.
Cleaning sequence starts when DI4 is high.
Cleaning sequence starts when DI5 is high.
Cleaning sequence starts when DI6 is high.
Starts pump cleaning.
Pump cleaning is not active.
Starts pump cleaning immediately.
Starts pump cleaning when DI4 goes high.
Starts pump cleaning when DI5 goes high.
Starts pump cleaning when DI6 goes high.
Source selection (see
Terms and abbreviations
83.11
specifies
curve.
curve.
83.15 Fixed time
on page 100). -
Def/FbEq16
4
0.0
10 = 1%
0
1 = 1
Cleaning
0
1
2
0b0000
interval.
Not active
0
1
2
3
4