ABB ACQ580 Firmware Manual page 211

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
DC voltage
Output power
Reserved
Speed ref ramp in
Speed ref ramp out
Speed ref used
Reserved
Freq ref used
Reserved
Process PID out
Other
36.02
PVL filter time
0.00...120.00 s
36.06
AL2 signal source
36.07
AL2 signal scaling
0.00...32767.00
36.09
Reset loggers
Done
All
PVL
AL2
36.10
PVL peak value
-32768.00...
32767.00
36.11
PVL peak date
-
36.12
PVL peak time
-
36.13
PVL current at peak
-32768.00...
32767.00 A
Description
01.11 DC voltage
(page 103).
01.14 Output power
(page 104).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
28.02 Frequency ref ramp output
40.01 Process PID output actual
Source selection (see
Terms and abbreviations
Peak value logger filtering time. See parameter
signal
source.
Peak value logger filtering time.
Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters 36.40...36.49. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
36.07 AL2 signal
Amplitude logger 2 can be reset using parameter
loggers. The logger is also reset whenever the signal
source or scaling is changed. The date and time of the last
reset are stored into parameters
respectively.
For the selections, see parameter
Defines the signal value that corresponds to 100% amplitude. 100.00
Signal value corresponding to 100%.
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Reset completed or not requested (normal operation).
Reset both the peak value logger and amplitude logger 2.
Reset the peak value logger.
Reset amplitude logger 2.
Peak value recorded by the peak value logger.
Peak value.
The date on which the peak value was recorded.
Peak occurrence date.
The time at which the peak value was recorded.
Peak occurrence time.
Motor current at the moment the peak value was recorded.
Motor current at peak.
(page 162).
(page 162).
(page 163).
(page 167).
(page 213).
on page 100). -
36.01 PVL
scaling.
36.09 Reset
36.50
and
36.51
36.01 PVL signal
Parameters 207
Def/FbEq16
7
8
9
10
11
12
13
14
15
16
2.00 s
100 = 1 s
Motor torque
source.
1 = 1
Done
0
1
2
3
0.00
1 = 1
01.01.1980
-
00:00:00
-
0.00 A
1 = 1 A