Essential Settings

Activation

Testing

4-14
Each drive on the DriveBus link must have an individual address in the
range of 1 to 12. The address – set with Parameter 70.01 –
corresponds to the DRNR setting in the DB and PC elements below.
For the DB and PC elements, the following settings are required:
DRB00
DRTYPEx
ACS600, AMC_classic, AMC_2, DSU_station,
(x = 1 to 12)
TSU_station, NO_DRIVE
ACSRX
DRNR
1 to 12 (Corresponds to drive address parameter 70.01)
EN
1
RESET
0
CNTRL
1
DS1
Number of data set (10 to 32)
WR1
1
I11
Transmit integer
I21
Transmit integer
I31
Transmit integer
The settings are similar for the ACS 600 Standard Drive, with the
exception of the available dataset numbers.
The ACSRX element starts to send datasets to the drive when the
WRx terminal is set to "1".
When the hardware part has been installed correctly it is possible to
test the communication via the link. The measurements can be carried
out using the FCB program. ACSRX has one terminal (ERR) which
indicates a fatal error on the link. (The value of "0" denotes "no error",
"1" corresponds to "error".) The reason for the error is given by another
terminal (ERRC) which produces an error code. The codes are listed in
the AC 80 PC Elements Reference Manual.