ABB ACQ580 Firmware Manual page 270

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

266 Parameters
No.
Name/Value
Supervision 1
Supervision 2
Supervision 3
Other [bit]
76.91
LC high level switch
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
Supervision 1
Supervision 2
Supervision 3
Other [bit]
76.92
LC low level action
No action
Warning
Fault
76.93
LC high level action
No action
Warning
Fault
76.95
Regulator bypass
control
Disable
Enable
Other [bit]
76.101 IPC parameter
synchronization
Enable
Disable
76.102 IPC synchronization
settings
Description
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects the source for digital high level switch.
High level switch is inactive.
High level switch is active.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects the action for drive to indicate when digital low level
switch is activated.
See parameter
76.90 LC low level switch
Low level switch is disabled and does not generate any event. 0
Low level switch generates
Low level switch generates
Selects the action for drive to indicate when digital high level
switch is activated.
See parameter
76.91 LC high level switch
High level switch is disabled and does not generate any
event.
High level switch generates
High level switch generates
Defines if direct-on-line pumps are automatically started and
stopped.
This setting can be used in applications with a low number of
sensors and low accuracy requirements.
Automatic starting and stopping is disabled.
Automatic starting and stopping is enabled.
Source selection (see
Terms and abbreviations
Defines parameter synchronization in IPC system.
Parameter synchronization is enabled.
Parameter synchronization is disabled.
Selects the settings that are synchronized between drives in
inverter-to-inverter communication bus.
The process PID and IPC parameters are synchronized.
Note: This parameter does not synchronize AI parameters.
(see page 184).
(see page 184).
(see page 184).
on page 100). -
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 184).
(see page 184).
(see page 184).
on page 100). -
(page 265).
0xD509 Low level
warning.
0xD403 Low level
fault.
(page 266).
0xD508 High level
warning.
0xD402 High level
fault.
on page 100). -
Def/FbEq16
8
9
10
Selected
0
1
2
3
4
5
6
7
8
9
10
Warning
1
2
Warning
0
1
2
Disable
0
1
Enable
0b0110