No.
Name/Value
37.41
ULC overload timer
0.0...10000.0 s
37.42
ULC underload
timer
0.0...10000.0 s
40

40 Process PID set 1

40.01
Process PID output
actual
-200000.00...
200000.00 PID
customer units
40.02
Process PID
feedback actual
-200000.00...
200000.00 PID
customer units
40.03
Process PID
setpoint actual
-200000...200000
PID customer units
40.04
Process PID
deviation actual
-200000.00...
200000.00 PID
customer units
Description
Defines the time for which the monitored signal must
continuously stay above the overload curve before the drive
takes the action selected by
Overload timer.
Defines the time for which the monitored signal must
continuously stay below the underload curve before the drive
takes the action selected by
Underload timer
Parameter values for process PID control.
The drive output can be controlled by the process PID. When
the process PID control is enabled, the drive controls the
process feedback to the reference value.
Two different parameter sets can be defined for the process
PID. One parameter set is in use at a time. The first set is
made up of parameters 40.07...40.50, the second set is
defined by the parameters in group
The binary source that defines which set is used is selected
by parameter
40.57 PID set1/set2
See also the control chain diagrams on pages
To set the PID customer unit, select Menu - Primary settings
- PID - Unit on the panel.
Displays the output of the process PID controller. See the
control chain diagram on page 414.
This parameter is read-only.
Process PID controller output.
Displays the value of process feedback after source
selection, mathematical function (parameter
feedback
function), and filtering. See the control chain
diagram on page 413.
This parameter is read-only.
Process feedback.
Displays the value of process PID setpoint after source
selection, mathematical function
function), limitation and ramping. See the control chain
diagram on page 413.
This parameter is read-only.
Setpoint for process PID controller.
Displays the process PID deviation. By default, this value
equals setpoint - feedback, but deviation can be inverted by
parameter
40.31 Set 1 deviation
chain diagram on page 414.
This parameter is read-only.
PID deviation.
37.03 ULC overload
actions.
37.04 ULC underload
actions.
41 Process PID set
selection.
413
and 414.
40.10 Set 1
(40.18 Set 1 setpoint
inversion. See the control
Parameters 213
Def/FbEq16
20.0 s
1 = 1 s
20.0 s
1 = 1 s
2.
-
1 = 1 PID
customer unit
-
1 = 1 PID
customer unit
-
1 = 1 PID
customer unit
-
1 = 1 PID
customer unit