Water Default - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

34 Default configuration

Water default

This is the default configuration of control connections for water and waste water applications.
Default control connections for the Water default
1...10 kohm
max.
500 ohm
4)
See the notes on
the next page.
X1
Reference voltage and analog inputs and outputs
1
2
3
AGND
4
5
6
AGND
7
8
9
AGND
X2 & X3
Aux. voltage output and programmable digital inputs
3)
10
11
DGND
4)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
RO1C
20
RO1A
21
RO1B
22
RO2C
23
RO2A
24
RO2B
25
RO3C
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
30
31
DGND
S4
TERM
S5
X4
Safe torque off
34
OUT1
35
OUT2
4)
36
SGND
37
38
X10
24 V AC/DC
40
24 V AC/DC+ in R6...R11 only: Ext. 24V AC/DC input to power up the
5)
41
24 V AC/DC- in
SCR
Signal cable shield (screen)
AI1
Output frequency/speed reference: 0...10 V
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Actual feedback: 0...10 V
Analog input circuit common
AO1
Output frequency: 0...10 V
AO2
Motor current: 0...20 mA
Analog output circuit common
+24V
Aux. voltage output +24 V DC, max. 250 mA
Aux. voltage output common
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Not configured
DI3
Constant frequency/speed selection
DI4
Not configured
DI5
Not configured
DI6
Not configured
Ready run
250 V AC / 30 V DC
2 A
Running
250 V AC / 30 V DC
2 A
Fault (-1)
250 V AC / 30 V DC
2 A
B+
Embedded fieldbus, EFB (EIA-485)
A-
Termination switch
BIAS
Bias resistors switch
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function in the Hardware
IN1
manual of the drive
IN2
control unit when the main supply is disconnected.