No.
Name/Value
80
80 Flow calculation and
protection
80.01
Actual flow
-200000.00...
3
200000.00 m
/h
80.02
Actual flow
percentage
-100.00...100.00%
80.03
Total flow
0.00...
21474836.00 m
80.04
Specific energy
0.00...
3
32767.95 m
/kWh
80.05
Estimated pump
head
0.00...32767.00 m
80.11
Flow feedback 1
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback data
storage
80.12
Flow feedback 2
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback data
storage
Description
Actual flow calculation.
Note: Parameters are dynamically hidden based on selection
of flow calculation mode. Parameters are visible according to
the selection of parameter
Actual system flow that is either calculated from the pressure
difference, measured directly or estimated from the pump
curves.
The calculation method is selected with parameter
Flow feedback
function.
See the control chain diagram on page 412.
Calculated flow.
Shows the percentage of parameter
80.15 Maximum
flow.
Flow percentage.
Shows cumulative calculated flow.
Total calculated flow.
3
Shows the ratio of pump flow rate and power input.
Specific energy of the pump.
Shows the estimated head produced by the pump.
Estimated pump head.
Selects the source for the flow feedback 1.
Feedback not used.
12.12 AI1 scaled value
12.22 AI2 scaled value
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
40.91 Feedback data storage
Selects the source for the flow feedback 2.
Feedback not used.
12.12 AI1 scaled value
12.22 AI2 scaled value
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
40.91 Feedback data storage
80.13 Flow feedback
80.01 Actual flow
(see page 125).
(see page 126).
(see page 122).
(see page 127).
(see page 127).
(see page 229).
(see page 125).
(see page 126).
(see page 122).
(see page 127).
(see page 127).
(see page 229).
Parameters 269
Def/FbEq16
function.
-
80.13
3
1 = 1 m
from
0.00
100 = 1%
0.00
3
1 = 1 m
0.00
3
1 = 1 m
/kWh
0.00
1 = 1 m
Not selected
0
1
2
3
8
9
10
Not selected
0
1
2
3
8
9
10
/h