ABB ACQ580 Firmware Manual page 215

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
Warning/Fault
37.11
ULC speed table
point 1
-30000.0...30000.0
rpm
37.12
ULC speed table
point 2
-30000.0...30000.0
rpm
37.13
ULC speed table
point 3
-30000.0...30000.0
rpm
37.14
ULC speed table
point 4
-30000.0...30000.0
rpm
37.15
ULC speed table
point 5
-30000.0...30000.0
rpm
37.16
ULC frequency
table point 1
-500.0...500.0 Hz
37.17
ULC frequency
table point 2
-500.0...500.0 Hz
37.18
ULC frequency
table point 3
-500.0...500.0 Hz
Description
The drive generates a warning
warning) if the signal stays continuously below the underload
curve for half of the time defined by parameter
overload
timer.
The drive trips on
8001 ULC underload fault
continuously above the underload curve for a time defined by
parameter
37.42 ULC underload
Defines the first of the five speed points on the X-axis of the
user load curve.
Speed points are used if parameter
is set to
Vector
or if
99.04 Motor control mode
and the reference unit is rpm.
The five points must be in order from lowest to highest. The
points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
Speed.
Defines the second speed point.
See parameter
37.11 ULC speed table point
Speed.
Defines the third speed point.
See parameter
37.11 ULC speed table point
Speed.
Defines the fourth speed point.
See parameter
37.11 ULC speed table point
Speed.
Defines the fifth speed point.
See parameter
37.11 ULC speed table point
Speed.
Defines the first of the five frequency points on the X-axis of
the user load curve.
Frequency points are used if parameter
mode
is set to
Scalar
and the reference unit is Hz.
The five points must be in order from lowest to highest. The
points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
Frequency.
Defines the second frequency point.
See parameter
37.16 ULC frequency table point
Frequency.
Defines the third frequency point.
See parameter
37.16 ULC frequency table point
Frequency.
(A8BF ULC underload
37.41 ULC
if the signal stays
timer.
99.04 Motor control mode
is set to
Scalar
1.
1.
1.
1.
99.04 Motor control
1.
1.
Parameters 211
Def/FbEq16
3
150.0 rpm
1 = 1 rpm
750.0 rpm
1 = 1 rpm
1290.0 rpm
1 = 1 rpm
1500.0 rpm
1 = 1 rpm
1800.0 rpm
1 = 1 rpm
5.0 Hz
1 = 1 Hz
25.0 Hz
1 = 1 Hz
43.0 Hz
1 = 1 Hz