348 Fault tracing
Code
Warning / Aux. code
(hex)
AFE9
Start delay
AFED
Run permissive
AFEE
Start interlock 1
AFEF
Start interlock 2
AFF0
Start interlock 3
AFF1
Start interlock 4
AFF6
Identification run
AFF8
Motor heating active
B5A0
STO event
Programmable event:
31.22 STO indication
run/stop
D405
Pipe fill-timeout
Programmable warning:
82.25 Soft pipe fill
supervision
D501
No more available
PFC motors
D502
All motors interlocked
D503
VSD controlled PFC
motor interlocked
0xD505
Max cleaning warning
Programmable warning:
83.35 Cleaning count
fault
Cause
The start delay is active and
the drive will start the motor
after a predefined delay.
Run permissive is keeping the
drive from running the motor.
Start interlock 1 is keeping the
drive from starting.
Start interlock 2 is keeping the
drive from starting.
Start interlock 3 is keeping the
drive from starting.
Start interlock 4 is keeping the
drive from starting.
Motor ID run will occur at next
start.
Pre-heating is being performed Informative warning.
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is lost.
Soft pipe fill is reached the
timeout limit. The PID output is
not reached the setpoint after
reference ramping is ended
and timeout limit is elapsed.
No more PFC motors can be
started because they can be
interlocked or in the Hand
mode.
All the motors in the PFC
system are interlocked.
The motor connected to the
drive is interlocked
(unavailable).
Maximum number of cleanings
are reached in defined time.
The Pump cleaning is unable
to clean the pump and hence,
manual cleaning is required.
What to do
Informative warning. See parameter
21.22 Start
delay.
Check the setting of (and source
selected by) parameter
permissive.
Check the signal source selected for
parameter
20.41 Start interlock
Check the signal source selected for
parameter
20.42 Start interlock
Check the signal source selected for
parameter
20.43 Start interlock
Check the signal source selected for
parameter
20.44 Start interlock
Informative warning.
Motor pre-heating is active. Current
specified by parameter
heating current
is being passed through
the motor.
Informative warning.
Check safety circuit connections. For
more information, see chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
31.22 STO indication
run/stop
(page 180).
Check the pipe for possible leakage.
See parameter
82.25 Soft pipe fill
supervision
and
82.26 Time-out
Check that there are no interlocked
PFC motors, see parameters:
76.81...76.84.
If all motors are in use, the PFC system
is not adequately dimensioned to
handle the demand.
Check that there are no interlocked
PFC motors, see parameters
76.81...76.84.
Motor connected to the drive is
interlocked and thus cannot be started.
Remove the corresponding interlock to
start the drive controlled PFC motor.
See parameters 76.81...76.84.
Check the pump for blockages.
Clean the pump manually if needed.
Check parameters
83.35 Cleaning
count fault
to
83.37 Maximum cleaning
count.
20.40 Run
1.
2.
3.
4.
21.16 Pre-
limit.