ABB ACQ580 Firmware Manual page 363

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
9084
External fault 4
(Editable message text)
Programmable fault:
External event 4 source
31.08 External event 4
type
9085
External fault 5
(Editable message text)
Programmable fault:
External event 5 source
31.10 External event 5
type
FA81
Safe torque off 1
FA82
Safe torque off 2
FF61
ID run
Cause
Fault in external device 4.
31.07
Fault in external device 5.
31.09
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Safe torque off function is
active, ie. STO circuit 2 is
broken.
Motor ID run was not
completed successfully.
0001 Maximum current limit too low.
0002 Maximum speed limit or
calculated field weakening
point too low.
Fault tracing 359
What to do
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
Check safety circuit connections. For
more information, see chapter The
Safe torque off function in the
Hardware manual of the drive and
description of parameter
indication run/stop
(page 180).
Check the value of parameter
Control board
supply.
Check the nominal motor values in
parameter group
99 Motor
Check that no external control system
is connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that no operation limits prevent
the completion of the ID run. Restore
parameters to default settings and try
again.
Check that the motor shaft is not
locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
Check settings of parameters
Motor nominal current
and
Maximum
current. Make sure that
30.17
> 99.06.
Check that the drive is dimensioned
correctly according to the motor.
Check settings of parameters
30.11 Minimum speed
30.12 Maximum speed
99.07 Motor nominal voltage
99.08 Motor nominal frequency
99.09 Motor nominal
Make sure that
30.12
> (0.55 × 99.09) >
(0.50 × synchronous speed)
30.11
< 0, and
• supply voltage > (0.66 × 99.07).
31.07
31.09
31.22 STO
95.04
data.
99.06
30.17
speed.