ABB ACQ580 Firmware Manual page 220

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

216 Parameters
No.
Name/Value
40.15
Set 1 output scaling
-200000.00...
200000.00
40.16
Set 1 setpoint 1
source
Not selected
Reserved
Internal setpoint
AI1 scaled
AI2 scaled
Reserved
Motor
potentiometer
Reserved
Freq in scaled
AI1 percent
AI2 percent
Control panel (ref
saved)
Control panel (ref
copied)
Description
See parameter
40.14 Set 1 setpoint
If the parameter is set to zero, scaling is automatic:
Operation mode
(see par. 19.01)
Speed control
Frequency control
Process PID controller output base.
Selects the primary source of process PID setpoint. See the
control chain diagram on page 413.
None.
Internal setpoint. See parameter
sel1.
12.12 AI1 scaled value
12.22 AI2 scaled value
22.80 Motor potentiometer ref act
potentiometer).
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
Panel reference
(03.01 Panel
saved by the control system for the location where the control
returns is used as the reference.
(Selection not available for parameter
source.)
Reference
Ext1 -> Ext2
Panel reference
(03.01 Panel
the previous control location is used as the reference when
the control location changes if the references for the two
locations are of the same type (eg
frequency/speed/torque/PID); otherwise, the actual signal is
used as the new reference.
Reference
Ext1 -> Ext2
scaling.
Scaling
46.01 Speed scaling
46.02 Frequency scaling
40.19 Set 1 internal setpoint
(see page 125).
(see page 126).
(output of the motor
(see page 122).
(see page 127)
(see page 127)
reference, see page 106)
71.16 Setpoint 1
Ext1 reference
Ext2 reference
Active reference
Inactive reference
t
reference, see page 106) for
Ext1 reference
Ext2 reference
Active reference
Inactive reference
t
Def/FbEq16
0.00
1 = 1
Internal
setpoint
0
1
2
3
4
5...7
8
9
10
11
12
13
14