ABB ACQ580 Firmware Manual page 255

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
58.25
Control profile
ABB Drives
DCU Profile
58.26
EFB ref1 type
Speed or frequency Type and scaling is chosen automatically according to the
Transparent
General
Reserved
Speed
Frequency
58.27
EFB ref2 type
58.28
EFB act1 type
Speed or frequency Type and scaling is chosen automatically according to the
Transparent
General
Reserved
Speed
Frequency
58.29
EFB act2 type
Description
Defines the communication profile used by the Modbus
protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
See section
About the control profiles
ABB Drives control profile (with a 16-bit control word)
DCU control profile (with a 16 or 32-bit control word)
Selects the type and scaling of reference 1 received through
the embedded fieldbus interface.
The scaled reference is displayed by
currently active operation mode as follows.
Operation mode
(see par. 19.01)
Speed control
Frequency control
No scaling is applied.
Generic reference without a specific unit. Scaling: 1 = 100.
Speed reference. The scaling is defined by parameter
Speed
scaling.
Frequency reference. The scaling is defined by parameter
46.02 Frequency
scaling.
Selects the type and scaling of reference 2 received through
the embedded fieldbus interface. The scaled reference is
displayed by
03.10 EFB reference
(The panel at the moment shows Torque as the default, which
cannot be used.)
Selects the type of actual value 1.
currently active operation mode as follows.
Operation mode
(see par. 19.01)
Speed control
Frequency control
No scaling is applied.
Generic reference without a specific unit. Scaling: 1 = 100.
Scaling is defined by parameter
Scaling is defined by parameter
Selects the type of actual value 2.
For the selections, see parameter
Parameters 251
58.06
settings).
on page 371.
03.09 EFB reference
Reference 1 type
Speed
Frequency
46.01
2.
Actual 1 type
Speed
Frequency
46.01 Speed
scaling.
46.02 Frequency
scaling.
58.28 EFB act1
type.
Def/FbEq16
ABB Drives
0
5
Speed or
frequency
1.
0
1
2
3
4
5
Speed or
frequency
Speed or
frequency
0
1
2
3
4
5
Transparent

Advertisement

Table of Contents
loading