134 Parameters
No.
Name/Value
CMOD-01
CMOD-02
CHDI-01
CPTC-02
15.03
DI status
Bit
Name
0
DI7
1
DI8
2
DI9
3
DI10
4
DI11
5
DI12
6...15
Reserved
0000h...FFFFh
15.04
RO/DO status
Bit
Name
0
RO4
1
RO5
2...4
Reserved
5
DO1
6...15
Reserved
0000h...FFFFh
Description
CMOD-01 multifunction extension module (external
24 V AC/DC and digital I/O).
CMOD-02 multifunction extension module (external
24 V AC/DC and isolated PTC interface).
CHDI-01 115/230 V digital input extension module.
Displays the status of the digital inputs DI7...DI12 on the
extension module
Bit 0 indicates the status of DI7.
Example: 001001b = DI7 and DI10 are on, remainder are off.
This parameter is read-only.
Description
1 = Digital input 7 is ON.
1 = Digital input 8 is ON.
1 = Digital input 9 is ON.
1 = Digital input 10 is ON.
1 = Digital input 11 is ON.
1 = Digital input 12 is ON.
Status of digital input/outputs.
Displays the status of the relay outputs RO4 and RO5 and
digital output DO1 on the extension module.
Bits 0...1 indicates the status of RO4...RO5; bit 5 indicates
the status of DO1.
Example: 100101b = RO4 is on, RO5 is off. and DO1 is on.
This parameter is read-only.
Description
1 = Relay output 4 is ON.
1 = Relay output 5 is ON
1 = Digital output 1 is ON.
Status of relay/digital outputs.