ABB ACQ580 Firmware Manual page 283

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
83.15
Fixed time interval
00:00:00...45:12:15
h
83.16
Cycles in cleaning
program
1...65535
83.20
Cleaning speed
step
0...100%
83.25
Time to cleaning
speed
0.000...60.000 s
83.26
Time to zero-speed
0.000...60.000 s
83.27
Cleaning on time
0.000...1000.000 s
83.28
Cleaning off time
0.000...1000.000 s
83.35
Cleaning count fault
No action
Warning
Fault
83.36
Cleaning count time
00:00:00...45:12:15
h
83.37
Maximum cleaning
count
0...30
Description
Defines the constant time interval between cleaning cycles.
This parameter is used only when cleaning is triggered by
time interval.
Time
Defines the number of cycles performed in cleaning program.
For example, 1 cycle = 1 forward + 1 reverse step.
Value range
Defines the speed/frequency step size in pump cleaning.
Cleaning speed step is same for positive and negative
directions.
Note: If you have disabled the negative rotation direction by
speed limits, the pump cleaning does not operate in the
negative direction.
Percentage of the cleaning speed/frequency value.
Defines the time required for the drive to reach cleaning
speed set by parameter
Time
Defines the time required for the drive to reach zero speed
from the cleaning speed set by parameter
speed
step.
Time
Defines the cleaning On time when the drive is running at
cleaning speed set by parameter
Time
Defines the cleaning Off time when the drive stays at zero
speed between positive and negative pulses and after one
cleaning cycle before starting a new cleaning cycle.
Time
Activates the cleaning count monitoring, and selects the
action it takes if it detects too many cleaning starts within the
time defined by parameter
See section
Cleaning count monitoring
No action
Warning
Fault
Defines the time for cleaning count monitoring.
See section
Cleaning count monitoring
Time
Defines the maximum cleaning counts allowed.
See section
Cleaning count monitoring
Maximum cleaning counts.
83.20 Cleaning speed
step.
83.20 Cleaning
83.20 Cleaning speed
83.36 Cleaning count
(page 56).
(page 56).
(page 56).
Parameters 279
Def/FbEq16
02:00:00h
1 = 1h
3
80
1 = 1%
3.000
1 = 1s
3.000
1 = 1s
10.000
step.
1 = 1s
5.000
1 = 1s
No action
time.
0
1
2
00:01:00h
1 = 1h
5
1 = 1