122 Parameters
No.
Name/Value
10.99
RO/DIO control
word
Bit
Name
0
RO1
1
RO2
2
RO3
3
RO4
4
RO5
5...7
Reserved
8
DIO1
9...15
Reserved
0000h...FFFFh
10.101 RO1 toggle counter
0...4294967000
10.102 RO2 toggle counter
0...4294967000
10.103 RO3 toggle counter
0...4294967000
11

11 Standard DIO, FI, FO

11.21
DI5 configuration
Digital input
Frequency input
11.38
Freq in 1 actual
value
0 ... 16000 Hz
11.39
Freq in 1 scaled
value
-32768.000...
32767.000
Description
Storage parameter for controlling the relay outputs eg.
through the embedded fieldbus interface. To control the relay
outputs (RO) of the drive, send a control word with the bit
assignments shown below as Modbus I/O data. Set the target
selection parameter of that particular data (58.101...58.114)
to
RO/DIO control
word. In the source selection parameter of
the desired output, select the appropriate bit of this word.
Description
Source bits for relay outputs RO1...RO3. See parameters 10.24,
10.27
and 10.30.
Source bits for relay outputs RO4...RO5 with a CHDI-01 or CMOD-01
extension module. See parameters
Source bit for digital output DO1 with a CMOD-01 extension module.
See parameter 15.23.
RO/DIO control word.
Displays the number of times relay output RO1 has changed
states.
State change count.
Displays the number of times relay output RO2 has changed
states.
State change count.
Displays the number of times relay output RO3 has changed
states.
State change count.
Configuration of the frequency input.
Selects how digital input 5 is used.
DI5 is used as a digital input.
DI5 is used as a frequency input.
Displays the value of frequency input 1 (via DI5 when it is
used as a frequency input) before scaling. See parameter
11.42 Freq in 1
min.
This parameter is read-only.
Unscaled value of frequency input 1.
Displays the value of frequency input 1 (via DI5 when it is
used as a frequency input) after scaling. See parameter
Freq in 1
min.
This parameter is read-only.
Scaled value of frequency input 1 (DI5).
Def/FbEq16
0000h
15.07
and.15.10.
1 = 1
-
1 = 1
-
1 = 1
-
1 = 1
Digital input
0
1
-
1 = 1 Hz
-
11.42
1 = 1