ABB ACQ580 Firmware Manual page 345

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Code
Warning / Aux. code
(hex)
A2B4
Short circuit
A2BA
IGBT overload
A3A1
DC link overvoltage
A3A2
DC link undervoltage
A3AA
DC not charged
A490
Incorrect temperature
sensor setup
A491
External temperature
1
(Editable message text)
A492
External temperature
2
(Editable message text)
A4A0
Control board
temperature
Cause
Short-circuit in motor cable(s)
or motor.
Excessive IGBT junction to
case temperature. This
warning protects the IGBT(s)
and can be activated by a short
circuit in the motor cable.
Intermediate circuit DC voltage
too high (when the drive is
stopped).
Intermediate circuit DC voltage
too low (when the drive is
stopped).
The voltage of the intermediate
DC circuit has not yet risen to
operating level.
Temperature cannot be
supervised due to incorrect
adapter setup.
Measured temperature 1 has
exceeded warning limit.
Measured temperature 2 has
exceeded warning limit.
Control board temperature is
too high.
(none) Temperature above warning
limit
1 Thermistor broken
Fault tracing 341
What to do
Check motor and motor cable for
cabling errors.
Check motor and motor cable
(including phasing and delta/star
connection).
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter Electrical
installation, section Checking the
insulation of the assembly in the
Hardware manual of the drive.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
Check the supply voltage setting
(parameter
95.01 Supply
that the wrong setting of the parameter
may cause the motor to rush
uncontrollably, or may overload the
resistor.
Check the supply voltage.
If the problem persists, contact your
local ABB representative.
Check the settings of temperature
source parameters
35.11
Check the value of parameter
Measured temperature
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
35.13 Temperature
1 warning
limit.
Check the value of parameter
Measured temperature
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
35.23 Temperature
2 warning
limit.
Check the auxiliary code. See actions
for each code below.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Contact an ABB service representative
for control board replacement.
voltage). Note
and 35.21.
35.02
1.
35.03
2.