346 Fault tracing
Code
Warning / Aux. code
(hex)
A8A2
RO toggle warning
A8B0
ABB Signal
supervision 1
(Editable message text)
Programmable warning:
32.06 Supervision 1
action
A8B1
ABB Signal
supervision 2
(Editable message text)
Programmable warning:
32.16 Supervision 2
action
A8B2
ABB Signal
supervision 3
(Editable message text)
Programmable warning:
32.26 Supervision 3
action
A8B3
ABB Signal
supervision 4
(Editable message text)
Programmable warning:
32.36 Supervision 4
action
A8B4
ABB Signal
supervision 5
(Editable message text)
Programmable warning:
32.46 Supervision 5
action
A8B5
ABB Signal
supervision 6
(Editable message text)
Programmable warning:
32.56 Supervision 6
action
A8BE
ULC overload
warning
Programmable fault:
37.03 ULC overload
actions
Cause
The relay output is changing
states faster than
recommended, eg. if a fast
changing frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
0001 Relay output 1
0002 Relay output 2
0003 Relay output 3
Warning generated by the
signal supervision function 1.
Warning generated by the
signal supervision function 2.
Warning generated by the
signal supervision function 3.
Warning generated by the
signal supervision function 4.
Warning generated by the
signal supervision function 5.
Warning generated by the
signal supervision function 6.
Selected signal has exceeded
the user overload curve.
What to do
Replace the signal connected to the
relay output source with a less
frequently changing signal.
Select a different signal with parameter
10.24 RO1
source.
Select a different signal with parameter
10.27 RO2
source.
Select a different signal with parameter
10.30 RO3
source.
Check the source of the warning
(parameter
32.07 Supervision 1
Check the source of the warning
(parameter
32.17 Supervision 2
Check the source of the warning
(parameter
32.27 Supervision 3
Check the source of the warning
(parameter
32.37 Supervision 4
Check the source of the warning
(parameter
32.47 Supervision 5
Check the source of the warning
(parameter
32.57 Supervision 6
Check for any operating conditions
increasing the monitored signal (for
example, the loading of the motor if the
torque or current is being monitored).
Check the definition of the load curve
(parameter group
37 User load
signal).
signal).
signal).
signal).
signal).
signal).
curve).