Fault Messages - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Fault messages

Code
Fault / Aux. code
(hex)
1080
Backup/Restore
timeout
1081
Rating ID fault
2310
Overcurrent
2330
Earth leakage
Programmable fault:
Earth fault
Cause
Panel or PC tool has failed to
communicate with the drive
when backup was being made
or restored.
Drive software has not been
able to read the rating ID of the
drive.
Output current has exceeded
internal fault limit.
In addition to an actual
overcurrent situation, this fault
may also be caused by an
earth fault or supply phase
loss.
Drive has detected load
unbalance typically due to
31.20
earth fault in motor or motor
cable.
Fault tracing 351
What to do
Request backup or restore again.
Reset the fault to make the drive try to
reread the rating ID.
If the fault reappears, cycle the power
to the drive. You may have to be
repeat this. If the fault persists,
contact your local ABB
representative.
Check motor load.
Check acceleration times in
parameter group
23 Speed reference
ramp
(speed control) or
reference chain
(frequency control).
Also check parameters
scaling,
46.02 Frequency scaling
46.03 Torque
scaling.
Check motor and motor cable
(including phasing and delta/star
connection).
Check there are no contactors
opening and closing in motor cable.
Check that the start-up data in
parameter group 99 corresponds to
the motor rating plate.
Check that there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter Electrical
installation, section Checking the
insulation of the assembly in the
Hardware manual of the drive.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
99.04 Motor control
mode.)
If no earth fault can be detected,
contact your local ABB
representative.