ABB ACQ580 Firmware Manual page 359

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
6481
Task overload
6487
Stack overflow
64A1
Internal file load
64A4
Rating ID fault
64A6
Adaptive program
64B1
Internal SSW fault
Cause
Internal fault.
Internal fault.
File read error.
Rating ID load error.
Error running the adaptive
program.
000A Program corrupted or block
non-existent
000C Required block input missing
000E Program corrupted or block
non-existent
0011 Program too large.
0012 Program is empty.
001C A non-existing parameter or
block is used in the program.
001D Parameter type invalid for
selected pin.
001E Output to parameter failed
because the parameter was
write-protected.
0023 Program file incompatible with
current firmware version.
0024
Other –
Internal fault.
Fault tracing 355
What to do
Reboot the control unit (using
parameter
96.08 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative
Reboot the control unit (using
parameter
96.08 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative
Reboot the control unit (using
parameter
96.08 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative
Contact your local ABB
representative.
Check the auxiliary code (format
XXYY ZZZZ).
"XX" specifies the number of the state
(00=base program) and "YY"
specifies the number of the function
block (0000=generic error).
"ZZZZ" indicates the problem.
Restore the template program or
download the program to the drive.
Check the inputs of the block.
Restore the template program or
download the program to the drive.
Remove blocks until the error stops.
Correct the program and download it
to the drive.
Edit the program to correct the
parameter reference, or to use an
existing block.
Edit the program to correct the
parameter reference.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
Adapt the program to current block
library and firmware version.
Contact your local ABB
representative, quoting the auxiliary
code.
Reboot the control unit (using
parameter
96.08 Control board
or by cycling power. If the problem
persists, contact your local ABB
representative.
boot)
boot)
boot)
boot)