ABB ACQ580 Firmware Manual page 133

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

No.
Name/Value
Reserved
Abs motor speed
used
Abs motor speed %
Abs output
frequency
Reserved
Abs motor torque
Abs output power
Abs motor shaft
power
External PID1 out
Reserved
AO1 data storage
AO2 data storage
Other
13.13
AO1 forced value
0.000...22.000 mA /
0.000...11.000 V
13.15
AO1 unit selection
V
mA
13.16
AO1 filter time
0.000 ... 30.000 s
Description
01.61 Abs motor speed used
01.62 Abs motor speed %
01.63 Abs output frequency
01.64 Abs motor torque
01.65 Abs output power
01.68 Abs motor shaft power
71.01 External PID act value
13.91 AO1 data storage
13.92 AO2 data storage
Source selection (see
Terms and abbreviations
Forced value that can be used instead of the selected output
signal. See parameter
13.02 AO force
Forced value for AO1.
Selects the unit for readings and settings related to analog
input AO1.
Volts.
Milliamperes.
Defines the filtering time constant for analog output AO1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Filter time constant.
(page 106).
(page 106).
(page 106).
(page 106).
(page 106).
(page 106).
((page 254).
(page 133).
(page 133).
on page 100). -
selection.
t
)
Parameters 129
Def/FbEq16
21...25
26
27
28
29
30
31
32
33
34...36
37
38
0.000 mA
1 = 1 unit
mA
2
10
0.100 s
1000 = 1 s