Diagnostics - ABB ACQ580 Firmware Manual

Pump control program
Hide thumbs Also See for ACQ580:
Table of Contents

Advertisement

108 Parameters
No.
Name/Value
05

05 Diagnostics

05.01
On-time counter
0...65535 d
05.02
Run-time counter
0...65535 d
05.03
Hours run
0.0...
429496729.5 h
05.04
Fan on-time
counter
0...65535 d
05.10
Control board
temperature
-100... 300 °C or °F Control board temperature in degrees Celsius or Fahrenheit.
05.11
Inverter
temperature
-40.0...160.0%
Description
Various run-time-type counters and measurements related to
drive maintenance.
All parameters in this group are read-only unless otherwise
noted.
On-time counter. The counter runs when the drive is
powered.
On-time counter.
Motor run-time counter in full days. The counter runs when
the inverter modulates.
Motor run-time counter.
Corresponding parameter to
hours, that is, 24 *
05.02
Hours.
Running time of the drive cooling fan. Can be reset from the
control panel by keeping Reset down for over 3 seconds.
Cooling fan run-time counter.
Measured temperature of the control board
Estimated drive temperature in percent of fault limit. The fault
limit varies according to the type of the drive.
0.0% = 0 °C (32 °F)
100.0% = Fault limit
Drive temperature in percent.
05.02 Run-time counter
value + fractional part of a day.
Def/FbEq16
-
1 = 1 d
-
1 = 1 d
in
-
10 = 1 h
-
1 = 1 d
-
1 = unit
-
1 = 1%