374 Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
5
EXT2
6
RUN_DISABLE
7
STOPMODE_RA
MP
8
STOPMODE_EM
ERGENCY_RAM
P
9
STOPMODE_CO
AST
10
RAMP_PAIR _2
11
RAMP_OUT_ZER
O
12
RAMP_HOLD
13
RAMP_IN_ZERO
14
REQ_LOCAL_LO
CK
16
FB_LOCAL_CTL
17
FB_LOCAL_REF
18
Reserved for
RUN_DISABLE_1
19
Reserved
20
Reserved
Value
State/Description
1
Select External control location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External control location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
1
Run disable. If the drive is set to receive the run enable
signal from the fieldbus, this bit deactivates the signal.
0
Run enable. If the drive is set to receive the run enable
signal from the fieldbus, this bit activates the signal.
1
Normal ramp stop mode
0
(no op) Default to parameter stop mode if bits 7...9 are all
0.
1
Emergency ramp stop mode.
0
(no op) Default to parameter stop mode if bits 7...9 are all
0.
1
Coast stop mode.
0
(no op) Default to parameter stop mode if bits 7...9 are all
0.
1
(no op)
0
Select ramp set 1 (Acceleration time 1 / Deceleration time
1).
1
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
0
Normal operation.
1
Halt ramping (Ramp Function Generator output held).
0
Normal operation.
1
Force Ramp Function Generator input to zero.
0
Normal operation.
1
Drive does not switch to local control mode (see
parameter
19.18 HAND/OFF disable
0
Drive can switch between local and external control
modes.
1
Local mode for control from the fieldbus is requested.
Steal control from the active source.
0
(no op)
1
Local mode for reference from the fieldbus is requested.
Steal reference from the active source.
0
(no op)
Not yet implemented.
source).